Page 10 - CSTE_Annual-Report_2017-18
P. 10

We Moved!
                  Shortly after the 2018 Annual Conference,  CSTE left its home of nearly 20 years in Chamblee, GA to move a few miles down
                 I-85 to Century Center (Brookhaven, GA). Situated near partners like Northrop Grumman and the CDC, the new office spans the
                 entire floor and can accomodate over 100 employees. It also boasts nine different meeting rooms, state-of-the-art technology,
                    and a visual style more representative of CSTE’s brand. We hope you’ll stop by to visit the next time you’re in Atlanta!

                                                                                                      Nelco Architecture, Inc.
                                                                                                       a licensed affiliate
                                                                                                        1170 Peachtree St. N.E.
                                                                                                        Suite 1700
                                                                                                         Atlanta, Georgia 30309
                                                           Council of State &
                                                                                                         404.881.1811
                                                                                                         Release History
                                                      Territorial Epidemiologists                        Date 01.12.18  Remark Issued for Tenant Review
                                                                                                             Issued for Pricing, Permit & Construction
                                                                                                             Issued for MEP Engineering
                                                                                                          01.26.18
                                                                                                          02.27.18
                                                                   2635 Century Center
                 Table of Contents                                2635 Century Parkway, N.E.                 This document is the property of NELSON. Do not
                                                                                                             distribute, modify or reproduce without the written
                                                                       Suite 700
                                                                                                              consent of NELSON.
 Building Information  Architectural Title Sheet                     Atlanta, GA 30345  Furniture Vendor
                      Life Safety Plan
                   I-1.1
                                                                                   CWC Office Furnishings
 Building Description - A multi-tenant, ten (10) story steel structure office building with glass
                      General Notes
                                                                                   4343 Northeast Expressway
                   I-1.2
                       Demolition Plan
                                                                                    Atlanta, GA 30340
                    I-1.3
                                                                      Council of State & Territorial Epidemiologists (CSTE)
                        Wall Details & Elevations
                        Reflected Ceiling Plan & Details
                                                                      2872 Woodcock Boulevard
                                                                                     Phone - 770.621.6654
                        Power/Communication Plan
 Fire Protection -  Fully Sprinklered
                                                                                     Email - kevin.magill@c-w-c.com
                                                                                     Fax - 770.491.6374
 High Rise - Yes; exceeds 75 feet per 2012 NFPA 101 Section 3.3.36.7
 facade. Building Construction Type per IBC-2012 Edition, Chapter 6 - Type IB  I-2 I-3.1 I-3.2 I-4 I-5 I-6 Partition Plan  Interior Planning & Design  Tenant Representation  Contact - Kevin Magill
                                                                      Suite 250
                         Finish & Restroom Accessory
                                                                      Atlanta, GA 30341
 Fire Alarm System - Yes
                                                                                      MEP Engineering
 Generator -  Yes
                                                                       Contact - Beverly Christner
 Number of Stories - 10 Stories
                                                                       Phone - 770.458.3811
 Typical Floor Area -  20,905 SF
                                                                                      S&S Engineers, LLC
                                                        1170 Peachtree Street, N.E.
                                                        NELSON
                          Millwork Elevations
 Building - 2012 International Building Code (IBC), with 2014, 2015, and 2018 Georgia
                                                                                      145 Church Street, N.E.
 Total Building Area - 209,048 SF
                                                                       Fax - 770.458.8516
                         Plans
 Date of Building Construction - 1982
                          Millwork Elevations
                                                                        Construction & Project Management
                                                         Atlanta, GA  30309
 2018 City of Chamblee Code Requirements
                                                                                       Marietta, GA 30060
  Plumbing - 2012 International Plumbing Code (IPC), with 2014 and 2015 Georgia Amendments
 Fire Safety - 2012 International Fire Code (IFC), with 2014 Georgia Amendments
  Mechanical - 2012 International Mechanical Code (IMC), with 2014 and 2015 Georgia Amendments
                                                         Contact - Anna Loxley
                          Millwork Sections
                                                          Email - aloxley@nelsononline.com/rhinkle@nelsononline.com
  Gas Piping - 2012 International Fuel Gas Code (IFGC), with 2014 and 2015 Georgia Amendments
                                                          Phone - 404.881.1811
                           Millwork Sections
                                                                         Savills Studley
                                                                         3424 Peachtree Road
                                                          Fax - 404.876.1289
                                                                                        Phone - 770.933.8842
 Amendments Electrical - 2017 National Electrical Code (NEC) (No Georgia Amendments)  I-7.1 I-7.2 I-8.1 I-8.2 Engineering Mechanical HVAC New Work Plan  Suite 1700 Architect - Robert Hinkle  Email - bchristner@cste.org  Suite 240 Contact - Les Saunders  Area of Construction  Council of State &
                         MD-1 Mechanical HVAC Demo Plan
  Energy - 2009 International Energy Conservation Code (IECC), with 2011 & 2012 Georgia
                                                                                        Email - les@sandsengr.com
                                                                                                                    Territorial
   Supplements & Amendments; ASHRAE / IESNA Standard 90.1 - 2007, with Georgia Amendments
                                                                         Suite 2100
                                                                         Atlanta, GA 30309
                                                                                                                     Epidemiologists
   Accessibility - Georgia Accessibility Code - GSFC Rules & Regulations, 120-3-20A, referencing the
                                                           Property Management
                                                                          Contact - Kevin Rodriguez
   Life Safety - NFPA 101-2012 Life Safety Code; as amended by Rules and Regulations of the Safety
                             Mechanical HVAC Schedules,
                                                           Highwoods Properties
                                                                          Phone - 404.504.0020
                                                           2200 Century Parkway, N.E.
                                                                                                                      2635 Century Center
    Fire Commissioner, Chapter 120-3-3 through the Georgia Department of Community Affairs
                                                                          Mobile - 678.687.3383
                             Schedules & Compliance Form
   2010 ADA (Americans with Disabilities Act)
                                                            Atlanta, GA 30345
    We certify that we have prepared these plans in conformity with Chapter 120-3-20A of the Rules and
     Regulations of the Georgia Safety Fire Commissioner referencing the 2010 ADA Standards for Accessible
                              Power/Communication Plan
                                                                                                                      Suite 700
     Design for making buildings and facilities accessible to and usable by people with disabilities to the best
                                                                                                                       Atlanta, GA 30345
                                                             Phone - 404.443.1851
                              Lighting Plan & Details
                                                             Email - mark.linnemeier@highwoods.com
                                                             Fax - 919.431.1459
    Georgia Accessibility Code  M-1 M-2 E-1 E-2 E-3  Details & Notes  Suite 250 Contact - Mark Linnemeier  Email - krodriguez@savills-studley.com  2635 Century Parkway, N.E.
     of our knowledge, information and belief for the scope of the work herein permitted.
                               Plumbing Notes, Schedules and
                                                                                                                       23,278 RSF
                              Plumbing Plan
      Project Information   P-1 P-2 Vicinity Map  Project Location                                                       Title Sheet A. Loxley 122051717_CD01_1
                               Riser Diagrams
       Project Summary and Scope - Interior alterations of second generation tenant space within a
       10-story multi-tenant building with generic tenant build-out.  Minimum demolition; considerable new
                                                                                                                            L. Roberts/T. Glover/R. Hinkle
       construction.  New plumbing locations to be installed, including new ADA compliant single-use restroom.
        HVAC test and balance shall be conducted.  Power and voice/data modifications are considerable.  New
                                                                                                                         Drawn By
                                                                                                                          Project Number 12205.1717
                                                                                                                         Checked By
        upgraded finishes to be installed throughout tenant suite, elevator lobby and common corridor.
                                                                                                                             02.27.18
         Occupancy Use and Classification per 2012 NFPA 101: Section 6.1.11; B - Business
                                                                                                                             I-1.1
        Area of Construction - 20,788 USF                                                                                 File ID Date Released for Construction
                                                                                                                           Sheet Number
          Maximum Occupant Load Calculation for the floor per 2012 NFPA 101:
          Stairs: 2 stairs of 46" are provided - 92"/ 0.3 per person=306 persons
         Occupancy Doors: (2) 36" doors (34" actual) are provided - 68"/ 0.2=340 persons           0 5 10  20  40  True North  of 13
          Maximum occupant load -  7th Floor = 306 persons
           Occupant Load Calculation for Suite 700:
                16,282 SF Office @ 100 SF/person = 163 persons
                741 SF Storage @ 500 SF/person = 1 person
            Actual (See Life Safety Plan on Sheet I-1.2 for furniture layout):
           Calculated:      Huddle #701 = 10 persons                  1  Key Plan
                 Huddle #702 = 10 persons
                 Huddle #707 = 13 persons
                  Conference #708 = 12 persons
                  Conference #711 = 39 persons
                  Huddle #716 = 10 persons
              Total Occupant Load: 163 + 1 + 10 + 10 + 13 + 12 + 39 + 10 + 8 + 13 + 8=
                                                                        Not to Scale
                  Huddle #737 = 8 persons
                   Huddle #744 = 13 persons
                   Huddle #760 = 8 persons
               287 persons > 306 persons
               Min. number of Means of Egress required from floor:  2 exits required, 2 exits provided
                Arrangement of Means of Egress:  1/3 diagonal distance per Section 7.5.1.3.3 (sprinklered)
                                       At this time, NELSON has only been engaged on this project to provide professional services limited to the
                                       preparation of construction documents, thereby allowing the Architect of Record limited involvement during the
                                       construction administration phase.  Due to this fact, Georgia Code requires us to include the following statement
                Max. Travel Distance:   300' (per Section 38.2.6.3)
                Max. Common Path of Travel:  100' (per Section 38.2.5.3.1)
                 Min. corridor width at Means of Egress:  44" (per Section 38.2.3.2; all corridors comply)
                 Min. door width: 32" (per Section 7.2.1.2.3; 36" wide doors provide 34" clearance and meet the 32"
               38: Exiting Requirements for a New Business Occupancy per 2012 NFPA 101 Chapter  Notice of Shared Responsibility  I-1.1  About CS TE  10
                Max. Dead End Corridor:  50' (per Section 38.2.5.2.1; corridors comply)
                                        "The Architect of Record and NELSON are not responsible for interpreting the intent of these construction
                                        documents, including making modifications as may be necessary during the construction phase; the Architect of
                  Fire Protection Requirements per 2012 IBC and 2012 NFPA 101:
                                        Record is no longer liable for the work where changes to these documents have been made."
                 requirement) Corridor Partitions - Non-rated per NFPA 101, Section 38.3.6.1(3) (sprinklered)  on our documents:
                  Tenant Demising walls - Non-rated per Section 508
                   Storage Rooms - Non-rated per IBC Table 508.4 (no separation required between B and S-1); NFPA 101
                  Occupancy Separation - N/A
                   Wall Penetrations - No Rating Required
                   Opening Protectives - Doors - No Rating Required
                   Floor Penetrations - Two hour rated
                    Sections 38.3.2.1/A38.3.2.1 and 39.3.2.1/A39.3.2.1